Microtek E2 SERIES 1KVA

Microtek High Frequency Online UPS provides Uninterrupted Pure Power for Critical Applications such as Computer Network, Servers, Cyber Cafes, etc.
These Products are manufactured in State-of-the-art automatic Manufacturing Plants equipped with Hi- Tech Machines in India.
Some of the important machines are SMT, ICT and Automatic Assembly Lines etc.
Microtek has won many Awards and recognition for its commitment to the industry.

Category:

Description

All Microtek Product Ranges are specially designed for the User’s Benefit.

Model E² Series
Rated Capacity 1 KVA / 800 Watts

Key Features

  • High Frequency and Hybrid Double Conversion Online Technology.
  • High End IGBT Based.
  • High End Micro Controller Based.
  • Wide Input Voltage Range
  • Advanced PFC Technology
  • Advanced Battery Management
  • Automatic Battery Charging in UPS Off Mode
  • Short Circuit and Overload Protection
  • Smart RS232 Communication with monitoring software
  • SNMP Card Slot (Optional)
  • Over Temperature Protection.
  • EMI / RFI Noise Filter
  • LCD/LED Display simultaneously
  • Specially designed to suit Indian Power and Environment Conditions
  • Generator Compatible (Supplying Sinewave Voltage)
  • Isolation Transformer (Optional)
  • Different Output Voltage settings.
  • Output Frequency fixed at 50Hz or can be synchronized with Input Frequency.
  • Static Bypass Enable or Disable.
  • Outlets Programmable and Non Programmable.
  • Protection from DC Fan failure.
  • In-built Over Voltage Cut-Off Device.

Warranty      One Year

NOTE: Product Specifications are subject to change without prior Notice.

Technical Specifications

Battery
DC Voltage 36 V
Charge Current 6.5 A
Input
Input Voltage Range (Load < 50%) 118 ~ 295 V (± 5 V)
Input Voltage range ((Load > 50%)) 160 ~ 295 V (± 5 V)
Frequency 40 ~ 70 Hz
Phase Single Phase with Ground
Power Factor ≥ 0.99 @ full load
Communication Interface RS232,SNMP (Optional)
Indication LCD Display
Noise Level Less than 50dBA @ 1 Meter (With Fan Speed Control)
UPS Overload / UPS Short-Circuit 110% / 300%
Output
Voltage Range 208 / 220 / 230 / 240 V AC
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Battery Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
THD (Linear Load) ≤ 2%
THD (Non Linear Load) ≤ 4%
Overload > 110%, 30s turn to Bypass Mode

> 150% instant turn to Bypass

Crest Factor 3:1 (Max)
Short Circuit Protection 5 cycles turn Off Inverter, no transfer to Bypass, provide Alarm (AC Mode), 5 cycles turn Off Inverter, provide Alarm(Battery Mode), Input Fuse blown or Breaker action
Waveform Pure Sinewave
Transfer Time

(AC Mode to Battery Mode)
(Inverter to Bypass Mode)

Zero

< 4 ms

Efficiency 85%~ 92%