Active power factor correction in all phases at input
50Hz/60Hz frequency converter mode
ECO mode operation for energy saving (ECO)
Emergency power off function (EPO)
Generator Compatible
SNMP+USB+RS-232 multiple communications
3-stage extendable charging design for optimized battery performance
Adjustable battery numbers 32-40 battery
Parallel can be done with either individual battery bank on each UPS, or with Common Battery Bank
Waveform (Battery Mode) : Pure Sine Wave
Weight
250kg
Dimensions (L W H)
60x79x160
Microtek offers 120KVA, 3PH:3PH, ±240V (40-Battery System) HF SUPERMAX+ (WITH 7 INCHES TOUCH PANEL LCD DISPLAY) Online Ups on World’s Latest Technology to meet the harsh Environmental and worst Power Conditions for Applications from Small Office requirement to Space Critical Missions with wide variety of Backup Range from 5 minutes to 10 hours to meet the needs of every individual.
Super Max+ series works on the principle of 3-level Inverter technology wich maximizes the efficiency by reducing conversion heat-loss and the 3-stage extendable charging design optimizes the battery performance. This series is generator compatible and parallel operation up to 4 units is possible. The communication feature over SNMP, USB and RS-232 is available.
Advantages of using Microtek Online UPS
Emergency Power Supply: - Whenever there is a power outage or shutdown, the UPS stands as a reliable and reliable power source. You can continue your work by using UPS or Batteries in the uncertain state of remote power disconnection.
Protects the Voltage Sensitive Device from Bad Electricity: - You can detect power fluctuations in variable power leading to damage to the gadgets. The uninterruptible power supply provides stable output by controlling power fluctuations.
Provides Surgical Protection: - In the event of a power outage, UPS detects improper power supply and stops direct power supply. Then it gives us stable energy from its stock. It prevents the cause of damage to the devices due to power supply interruptions.
Battery Life Save: - You can continue working in operating mode even when the power is off as it keeps charging every time you connect the UPS to the battery.
KEY FEATURES
True double-conversion
DSP technolozy guarantees high performance
Output power factor 1
Active power factor correction in all phases at input
50Hz/60Hz frequency converter mode
ECO mode operation for energy saving (ECO)
Emergency power off function (EPO)
Generator Compatible
SNMP+USB+RS-232 multiple communications
3-stage extendable charging design for optimized battery performance
Adjustable battery numbers 32-40 battery
Parallel can be done with either individual battery bankon each UPS, or with Common Battery Bank
Waveform (Battery Mode) : Pure Sine Wave
BENEFITS
Smart 7 Inch touch Panel LCD display in 120KVA
EMI Protection Available (C-3 Leval)
±6KVA Surge Protection available at Input across R/S/T-N & R/S/T/N-G
3 Stage Extendable Charging for optimized battery performance
Dual-Input design for easy of connecting 2 UPS in hot-standby or to provide other secondary source on the bypass input.
MODEL SUPER MAX+ 120 KVA HIGH FREQUENCY ONLINE UPS with 7 Inch LCD Touch Display
AC MODE: (100%-110% : 60Min) (110%-125%:10Min) (126%~150%:1Min) >150% for 400ms BATTERY MODE:(100%-110%:60Min) (110%-125%:10Min) (126%~150%:1Min) >150% for 400ms
PARALELL CAPACITY
Up to 4 units in parallel with Either Common battery bank or Separate battery bank
TRANSFER TIME
AC MODE TO BATTERY MODE
ZERO
INVERTER TO BYPASS
ZERO
WAVEFORM (BATTERY MODE)
PURE SINE WAVE
EFFICIENCY
AC MODE: 95.5% / ECO MODE: 98.5%, BATTERY MODE: 94.5%
BATTERY
BATTERY TYPE
SMF (VRLA)/ LEAD ACID BATTERIES
NUMBERS OF BATTERY
Default: 32 Nos. - Adjustable: 40 Nos.
CHARGING CURRENT (MAX.)
2A~36A(Adjustable)
CHARGING VOLTAGE
+/- 13.65V*N (N=16~20)
ALARM
BATTERY MODE
Sounding every 4 seconds
LOW BATTERY
Sounding every seconds
OVERLOAD
Sounding twice every seconds
FAULT
Continuously Sounding
PHYSICAL
DIMENTIONS PRODUCT (DxWxH)
97.4 x 60 x 160 (in mm)
NET WEIGHT PRODUCT (Kgs)
250 Kgs.
WARRANTY
1 Year Product Warranty
ENVIRONMENT
OPERATING HUMIDITY / TEMP.
<95% & Non-Condersing / 0.40°C
NOISE LEVEL / INGRESS PROTECTION (IP RATING)
Less Than 75dB @ 1 Meter / IP-20
LCD INDICATION
UPS status, Load percentages & amperes on each phase at output, Output VA & Wattage in each phase. Battery level(Charging ampere & discharging ampere), Input/Output voltage (Phase to Neutral & phase to phase information), Input Line Current per phase, Input VA/Wattage/PF per phase, Temprature information, Data Log events(max 500 events) and Fault conditions.
MANAGEMENT
SMART RS-232 OR USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10 Linux & Mac
OPTIONAL SNMP
Power Management From SNMP Manager and Web Browser